GeniSys™ 12VModel 7556Advanced 12 Vdc Burner ControlDescription / ApplicationsThe Beckett GeniSysTM 12V Advanced Burner Control is a 12 Vdc primary sa
2Table 1 - Model GuideBeckett GeniSys12V Control Part No.LockoutTimeValve-ondelay time1Motor-offdelay time17556A 0000115 sec 0 sec 0 sec7556P 1530115
3GeniSys 12V Control Installation and Operation ManualMounting:Mount the control on a 4” x 4” junction box on the burner, or inside the equipment cabi
4Figure 2 – Typical Wiring for Interrupted Ignition (With or without Valve-on Delay or Motor-off Delay.)Figure 1 – Getting to know the controlCad Cell
5GeniSys 12V Control Installation and Operation ManualIf the burner or control fails any of the following tests, recheck control wiring. If the burne
6Sequence of OperationBurner StatesStandby: The burner is idle, waiting for a call for heat. Valve-On Delay: The igniter and motor are on while the co
7GeniSys 12V Control Installation and Operation ManualPriming the PumpTo reset, interrupt power for at least 2 seconds.Always verify the control funct
Form No. 61703 R04, Printed in USA 08/10CORPORATIONUSA: P.O. Box 1289 ● Elyria, OH 44036Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road